A power grid with multiple voltage levels can be modelled using a multilayer network. A graph in each layer represents all the cables at the same voltage level. A directed bipartite for a pair of adjacent layers consists of transformers connecting two voltage levels.

mgrid provides an interface for modelling power grids and conduct power system analysis using pandapower and PyPSA. Though the way to build models (define buses, and connect them with transformers & cables, …) is similar, syntax is very different.

I have wrapped up my 5 months work at Utiligize, and build a package, mgrid, for power system analysis.

Topology, Element, Snapshot

Here, information for power system analysis is separated into three parts. The most basic part about a power grid is topology, how buses are connected. A class based on directed graph model in networkx package is used to store such information. This way, many existing methods and functions in networkx can be utilised directly. Bus is an imaginary concept to enforce Kirchhoff’s law. There is no power loss within any bus. It is not necessary to distinguish buses as PQ, PV, or slack.

The OpenDSS software (EPRI2021penDSS) divides electrical devices in power grids into two categories. The most basic one, called delivery element, has two terminals and moves electricity from one bus to another. Cables and transformers fit into this category. Any edge in topology corresponds to one and only one delivery element, and vice versa. The second category is conversion element, which converts electricity from or to another energy form. Such devices have only one terminal and must be connected to a bus. Such categorisation method is applied here.

In pandapower or PyPSA, different models for cables, for example, are built using one function (method). There are many optional arguments in such functions, which can be confusing. In mgrid, any element model can be modelled by a Python class. For example, one-line equivalent model for poly-phase cables is mgrid.power_flow.delivery.Cable, while detailed version for 3-phase cables is mgrid.power_flow.delivery.Cable3Phase. The number of optional arguments is largely reduced. Though classes are different, for delivery or conversion elements, methods to add them to a grid are the same. For example, Cable.update_pandapower, Cable3Phase.update_pandapower, and TransformerStd.update_pandapower both take a pandapower network and two terminals as arguments. Moreover, how to add element is entirely specified in update_pandapower. This feature makes it easier for users to define their own class. The function to build a pandapower network in mgrid will always use update_pandapower to add the element.

The last part takes time-variance into account. One snapshot consists of one set of nodal injections and one set of voltages. It is assumed that the grid remains steady state during the period which the snapshot specifies. At least in power flow calculation, adjacent snapshots do not have an impact. However, in terms of multiple snapshots, it is beneficial to consider snapshots together because voltage results from the previous snapshot can be used as the initial guess, which reduces the number of iterations. Data-frames with multi-level indices are used to store such information in mgrid. That way, any snapshot or series of results for any bus can be easily cross-sectioned using pandas.DataFrame.xs.

Multilayer Network

There are two kinds of edges in a multilayer network. Any intra-edge can only exist in a single layer and correspond to cables. Inter-edges connect layers and correspond to transformers in terms of power grids. Such two kinds of edges and the correspondence between voltage levels and layers are the two most useful features.

A multilayer network can be represented in three ways. The first one, with multiple graphs for different layers and directed bipartites for inter-edges, is mentioned in the introduction. Then, as introduced in bianconi2018multilayer, supra graph integrates intra-edges in different layers and inter-edges in one graph. This format is used when modelling power grids using dedicated power system analysis software. The last one is called planar graph here, and it contracts inter-edges in the supra graph. That way, inter-edges, representing transformers, become inter-nodes. Datasets for power grids are usually structured in this manner because transformers look like points geographically.

Usually, nodes are replicated in different layers. bianconi2018multilayer However, here, all the intra-nodes are unique, and inter-node pairs are distinguished by suffixes, which makes the supra graph format easier to be derived. This assumption reflects the reality that buses tend to locate in different geographical points. The disadvantage is that some algorithms designed for multilayer networks might be inapplicable.

Distributed External Grids

There are multiple 150-60 kV transformers in some subcomponents, connecting to external grids. Though their RPIs can be known from DC OPF, one or a set of them must be chosen as slack bus(es) in AC power flow.

AC power flow for with distributed slack has been implemented in PyPSA only. To use pandapower, one and only one 150-60 kV transformer should be chosen as the slack bus. Participation factors resulted from automatic generation control (AGC) can be used as weights for a set of buses with generators.

What if Divergence

For power flow calculation, it is hard to know the reason when the iteration diverges. To debug, we can divide the grid into smaller parts and calculate power flow individually. After detecting the part(s) which result(s) in the divergence, it can be excluded in the original grid. Conversion elements can be attached to the bus, which represents the excluded part. That way, the calculation for the grid will converge, and the error is merely the loss along cables and transformers in the excluded part.

Voltage Drop

The direct impedance method can be easily used for radial distribution feeders (RDF) to calculate voltage drops. Then, with the voltage at root known after power flow for higher voltage levels, voltages can be calculated accordingly.

The nonlinear relationship between complex voltages \( \overline{\boldsymbol{V}} \) and PRIs \( \overline{\boldsymbol{I}} \) can be expressed using bus impedance matrix: $$ \begin{aligned} \overline{\boldsymbol{V}} = \overline{\boldsymbol{Z}} \overline{\boldsymbol{I}} + \overline{\boldsymbol{V}}_\text{zero} \end{aligned} $$ where vector \( \overline{\boldsymbol{V}}_\text{zero} \) is for zero-load snapshot.

It might be problematic to apply the direct impedance method for high-voltage lines, because they should be modelled using one-line equivalent Pi models. The current loss must be taken into account.